Installing solid fuel heaters

By - , Build 109

Incorrect installation of solid fuel heaters has resulted in many minor to major fires, so it pays to get it right.

Figure 2: Example of a tested flue system (from AS/NZS 2918:2001).
Figure 1: Clearance locations for solid fuel heaters. ‘A’ and ‘B’ are floor protector dimensions given by the manufacturer.
Figure 3: Clearances for an untested flue system, plan and elevation. Note the ventilated air gaps (from AS/NZS 2918:2001).
Figure 4: Air gaps at bottom of flue shields (modified from deleted standard NZS 7421). Refer to manufacturers literature for specific clearances.

Fires started by the incorrect installation of solid fuel heaters are not always obvious. Some only result in a small amount of charring while others cause total destruction. Sometimes, minor charring of combustible materials is only identified if the building is being renovated and linings are removed, or some building failure occurs that exposes the structure. Better then to follow some guidelines and avoid the possibility of heat-sensitive materials catching alight.

Compliance document

Installation of solid fuel heaters is regulated by the New Zealand Building Code compliance document C/AS1 Part 9: Outbreak of fire. This calls for compliance with AS/NZS 2918:2001 Domestic solid fuel burning appliances – installation.

Figure 1: Clearance locations for solid fuel heaters. ‘A’ and ‘B’ are floor protector dimensions given by the manufacturer.

The two main principles controlling the installation of solid fuel heaters are clearances and ventilation.

Clearances

All solid fuel heaters should include manufacturers installation instructions that give minimum distances from walls and other heat-sensitive materials. These instructions should be strictly followed to ensure the materials are not overheated, causing them to ignite.

Complying with clearances for free-standing heaters is straightforward (see Figure 1). Clearances can vary from heater to heater, but Figure 1 shows where these are applicable. ‘A’ and ‘B’ are floor protector dimensions given by the manufacturer.

Flue clearances are also important, but unless a manufacturer offers a tested flue system, flue clearances must comply with those specified in AS/NZS 2918. For examples of a tested and an untested flue system, see Figures 2 and 3, respectively. The principle of an untested flue system is to provide a clearance between the two-flue shield, the outer flue shield and heat sensitive materials.

Ventilation

Clearances not only separate the heater or flue from heat-sensitive materials, but they also allow air to circulate between the appliance and the building. This means either leaving the shields open at the ends or where the shield rests against a plate, providing cut outs so that air can circulate between the annular spaces (see Figure 4).

Figure 2: Example of a tested flue system (from AS/NZS 2918:2001).

Where the heater has been installed in an enclosure, a heater must have been tested to AS/NZS 2918 Appendix B, which will result in specific clearance distances to heat-sensitive materials, e.g. timber framework. In addition, any enclosure must be ventilated with openings at the top and bottom.

Figure 3: Clearances for an untested flue system, plan and elevation. Note the ventilated air gaps (from AS/NZS 2918:2001).

These openings must be at least 10,000 mm2, which is equivalent to a 100 × 100 mm square opening, a 50 × 200 mm rectangular opening; or a 113 mm diameter hole.

Checklist

A few points to remember:

  • Install the appliance in accordance with the manufacturer’s instructions. Any deviation needs to be reviewed by a competent person who understands the principles of the installation, such as a registered installor with the NZ Home Heating Association.
  • Be wary of installing in enclosures with timber or other heat-sensitive materials.
  • Ensure that clearances are adequate and ventilation is provided for the flue and heater.
  • Don’t forget the floor protector (thickness and projection from the heater) and the flue extensions from the roof (see Figure 4).
Figure 4: Air gaps at bottom of flue shields (modified from deleted standard NZS 7421). Refer to manufacturers literature for specific clearances.

Download the PDF

More articles about these topics

Articles are correct at the time of publication but may have since become outdated.

Figure 2: Example of a tested flue system (from AS/NZS 2918:2001).
Figure 1: Clearance locations for solid fuel heaters. ‘A’ and ‘B’ are floor protector dimensions given by the manufacturer.
Figure 3: Clearances for an untested flue system, plan and elevation. Note the ventilated air gaps (from AS/NZS 2918:2001).
Figure 4: Air gaps at bottom of flue shields (modified from deleted standard NZS 7421). Refer to manufacturers literature for specific clearances.

Advertisement

Advertisement